DISCONTINUED - Zennio KNX-IP Interface  Pless
ZENNIO ZSY-IPI-PL

DISCONTINUED - Zennio KNX-IP Interface Pless

Product code: ZSY-IPI-PL
Zennio KNX-IP Interface Powerless allows programming or monitoring a device in a KNX subnetwork (line or area) from the IP network (PC, BMS system...) by using KNXnet/IP Tunneling protocol.
Price (Excluding GST)
$P.O.A

Description

  • KNXnet/IP tunneling protocol (up to 4 connections).
  • 6 status LED.
  • Manual function enable/disable button.
  • Ethernet 10/100 BaseT IP.
  • RJ45 socket.
  • Powered by the Bus (up to 34mA current draw)
  • Dimensions: 90 x 70 x 35mm (2 DIN units).
  • DIN rail unit assembly (EN 50022), with snap fit clamp.
  • KNX BCU integrated.
  • CE directives compliant.


Technical Details

Specification

General System Specifications
  • KNX Power Supply: 29V DC
  • KNX Max current consumption: 34.6mA @ 29VDC 
  • Ambient temperature: From -5 °C to +45 °C
  • Assembly: Independent control assembly device to be mounted inside distribution boxes or electrical panels. 
  • Status LED :
    • Ethernet line: Green (Ethernet line OK), red (manual overwrite active), OFF (error)
    • KNX line: Green (KNX line OK), OFF (error or not connected), red (default values reset),blinking green (boot mode)
    • Ethernet line traffic: Blinking: green (traffic on Ethernet line), red (error), OFF (no traffic)
    • KNX line traffic: Blinking: green (traffic on KNX line), red (error), OFF (no traffic) 
    • Group address (GA): OFF (normal operation), red (default values reset) 
    • Physical address (PA): OFF (normal operation), red (programming mode active), blinking red (Ethernet cable not connected)
  • IP Connector - Ethernet connector: RJ45
  • P Connector -  IP communication: Ethernet 10/100 BaseT (up to 10Mbits) 